Features

 

G35T10KF2B4S Features

MGE Galaxy 3500 10kVA 208V with 2 Battery Modules Expandable to 4, Start-up 5X8 10-40kVA compact 3 phase UPS power protection with excellent efficiency and optimized footprint particularly adapted for demanding industrial environments. Includes: Battery modules ship installed, Bolt down brackets, CD with software, Installation guide, Network Management Card, Power modules ship installed, Smart UPS signalling RS-232 cable, Start-Up Service, User Manual
 

Specifications

Specifications

  • Key Features
  • Output power capacity 8.0kWatts / 10.0kVA
  • Nominal Output Voltage 208V 3PH
  • Nominal Input Voltage 208V 3PH
  • Input Connections Hard Wire 5-wire (3PH + N + G)
  • Manageability
  • Built-in Web/SNMP management Full-featured management via a Web browser as well as comprehensive management from a Network Management System.
  • Environmental monitoring Prevent equipment failure from a full range of threatening environmental conditions.
  • LCD graphics display Text and mimic diagrams that display modes of operation, system parameters and alarms.
  • Audible alarms Provides notification of changing utility power and UPS power conditions
  • Availability
  • Parallel-capacity capable Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
  • Advanced electrical features Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency
  • Frequency and voltage regulation Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
  • Automatic internal bypass Supplies utility power to the connected loads in the event of a UPS power overload or fault.
  • Generator compatible Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • Dual mains input Increases availability by allowing the UPS to be connected to two separate power sources.
  • Hot-swappable batteries Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
  • Serviceability
  • User-replaceable air filters Enables quick and simple replacement of air filters.
  • Battery replacement without tools Enables fast battery replacement, lowering Mean Time to Repair (MTTR).
  • Front-access servicing Simplifies installation and UPS maintenance while minimizing space requirements.
  • Multiple levels of service With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you.
  • Technical support Our experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it.
  • EU CoC for UPS Ensures that UPSs sold in the EU are highly efficient
  • Total Cost of Ownership
  • Input power factor correction Minimizes installation costs by enabling the use of smaller generators and cabling.
  • Excellent footprint Small UPS footprint provides maximum usage of valuable electrical room floorspace
  • Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature.
  • Output
  • Max Configurable Power (Watts) 8.0kWatts / 10.0kVA
  • Output Voltage Note Configurable for 200 : 208 or 220V 3 Phase nominal output voltage
  • Output Voltage Distortion Less than 3%
  • Output Frequency (sync to mains) 57 - 63 Hz for 60 Hz nominal
  • Output Frequency (not synced) 60Hz +/- 0.1% for 60Hz nominal
  • Load Crest Factor Unlimited
  • Topology Double Conversion Online
  • Waveform type Sine wave
  • Output Voltage THD < 2% linear load and <4% non-linear load
  • Bypass Built-in Maintenance Bypass, Built-in Static Bypass
  • Input
  • Input frequency 40 - 70 Hz (auto sensing)
  • Input voltage range for main operations 160 - 240V
  • Input Power Factor at Full Load 0.98
  • Batteries & Runtime
  • Battery type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
  • Included Battery Modules 2
  • Typical recharge time 5hour(s)
  • Nominal Battery Voltage +/-192 V (split battery referenced to neutral)
  • Battery Slots Empty 2
  • Expected Battery Life (years) 3 - 5
  • RBC Quantity 2
  • Battery Charge Power (Watts) 983Watts
  • Battery Volt-Amp-Hour Capacity 4927
  • End of Discharge Battery Voltage +/-154 V
  • Runtime View Runtime Graph View Runtime Chart
  • Efficiency View Efficiency Graph
  • Communications & Management
  • Interface Port(s) DB-9 RS-232, G35T
  • Pre-Installed SmartSlot™ Cards AP9631
  • Physical
  • Maximum Height 58.7inches (1491MM, 149.1CM)
  • Maximum Width 20.6inches (523MM, 52.3CM)
  • Maximum Depth 33.0inches (838MM, 83.8CM)
  • Net Weight 913.0lbs. (415.0KG)
  • Shipping weight 981.0lbs. (445.92KG)
  • Shipping Height 64.7inches (1643MM, 164.3CM)
  • Shipping Width 25.6inches (650MM, 65.0CM)
  • Shipping Depth 41.8inches (1062MM, 106.2CM)
  • Environmental
  • Operating Temperature 32 - 104 °F (0 - 40 °C)
  • Operating Relative Humidity 0 - 95 %
  • Operating Elevation 0-3333ft (0-999.9meters)
  • Storage Temperature -15 - 45 °C
  • Storage Relative Humidity 0 - 95 %
  • Storage Elevation 0-50000ft (0-15000meters)
  • Audible noise at 1 meter from surface of unit 51.3dBA
  • Online thermal dissipation 1938.0BTU/hr
  • Protection Class NEMA 12, IP 51
  • Conformance
  • Approvals cUL Listed, CSA, CSA C22.2 No. 107.1, ISO 14001, ISO 9001, UL 1778
  • Standard warranty 1 year repair or replace
  • Sustainable Offer Status
  • RoHS Compliant
  • REACH REACH: Contains SVHCs
  • Proposition 65 Warning Available in Documentation tab