Inline current meter used to retrofit Basic rPDUs with remote power and environmental monitoring to obtain real-time metrics locally or over an IP network. Simply insert the unit between the rPDU and the power source to view power data on a local power meter and connect to the network to gather power data remotely.
Reliable power distribution with local and remote power monitoring options offer quick access to critical power usage information to evaluate energy usage trends and maximize uptime.
Environmental monitoring capabilities with the addition of optional environmental sensors ensure users have critical infrastructure data at their fingertips to prevent climate-related equipment failure and system downtime.
Every unit is 100% tested for reliability and functionality.
Simple and convenient configuration options for cord lengths and chassis colors.
Fault-Tolerant
Daisy Chaining with RSTP
simplifies intelligent rPDU
connectivity and ensures data
is reported even when a break
in the network chain occurs. Supports up to 40 rPDUs.
Specifications
Specifications
Product Specifications
MonitoringInput power monitoring. Environmental monitoring via optional remote sensors. Daisy chain Ethernet connectivity. Local high visibility LED display.
Monitoring Level 1Aggregate - Total Unit Monitoring (kWh, W, VA, PF)
Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 at 1% Accuracy Class Requirements
Monitoring Level 2Phase (A, B, C) Monitoring (kWh, W, VA, PF, V, A)
Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 at 1% Accuracy Class Requirements
VLC SupportYes
Quantity Of Inputs1
Voltage120/208V WYE
Current30A x 3 Phase WYE
VA per Input (Load Capacity)8.6kW
Frequency50/60Hz
Scrolling / Rotatable Digital DisplayYes
Power Cable Wire Gauge10/5
Power Cable Length-Receptacle Attached10ft
Power Cable Length-Plug Attached10ft
Plug TypeNEMA L21-30P Twistlock
Receptacle/Socket Type #1NEMA L21-30R
- Quantity on Face1 - Cord Attached
- StyleIndividual - Cord Attached
- Voltage per Receptacle/Socket120/208 3 Phase WYE
Remote Sensor RJ Connection Jacks1 (Supports up to 4 Sensors)
Continuous Operating Temperature RangeFull nameplate operation: 10-45C / 50-113F
Continuous Operating Temperature Range50% derated operation: 45-60C / 113-140F (See product manual or quick-start guide for full de-rated operating conditions)