Upgradeable Switched Outlet Level Monitored rPDUs provide reliable power distribution to critical IT equipment while delivering individual outlet level control and a comprehensive view of outlet level power usage via remote network access. Includes environmental monitoring capabilities to obtain real-time environmental metrics. With the Geist Upgradeable hot-swap technology, users may easily update the rPDU technology with the addition of the appropriate Interchangeable Monitoring Device (IMD) as business needs change.
Remotely reboot outlets to power cycle unresponsive IT equipment or increase runtime of critical equipment upon power failure with outlet-level control.
Reliable power distribution with local and remote outlet-level power monitoring options offer quick access to critical power usage information down to the device level to evaluate energy usage trends and maximize uptime.
Environmental monitoring capabilities with the addition of optional environmental sensors ensure users have critical infrastructure data at their fingertips to prevent climate-related equipment failure and system downtime.
Fault-Tolerant
Daisy Chaining with RSTP
simplifies intelligent rPDU
connectivity and ensures data
is reported even when a break
in the network chain occurs. Supports up to 40 rPDUs.
Daisy-chain up to 50 devices on a single IP address and reduce deployment time with self-configuration of downstream devices.
Specifications
Specifications
Product Specifications
MonitoringInput and Outlet power monitoring with Outlet switching. Circuit/Breaker current monitoring. Environmental monitoring via optional remote sensors. Daisy chain Ethernet connectivity. Local high visibility LED display.
Input MonitoringTotal Unit Monitoring (kWh, W, VA, PF)
Phase (AB, BC, CA) Monitoring (kWh, W, VA, PF, V, A)
Line (A, B, C) Monitoring (A)
Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 at 1% Accuracy Class Requirements
Circuit MonitoringCircuit / Breaker Monitoring (A)
Circuit/Breaker Current Measurements Independently Tested and Verified at 2% Accuracy
Outlet MonitoringOutlet Monitoring (kWh, W, VA, PF, V, A)
Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 at 1% Accuracy Class Requirements.
Remote Power ManagementIndividual Outlet Switching with Optional User Defined Time Delays and Sequential Power-up
VLC SupportYes
Quantity Of Inputs1
Voltage200-240V Delta
Current60A x 3 Phase DELTA
VA per Input (Load Capacity)17.2kW (208V)
Frequency50/60Hz
Over Current Protection(6) 20A Double Pole Magnetic Breakers (10kAIC Rated)
SwitchBreaker/Switch Combination
Scrolling / Rotatable Digital DisplayYes
Indicators - LED(s)24
Power Cable Wire Gauge4/4
Power Cable Length10ft / 3m
Power Entry LocationBottom Front
Plug TypeIEC60309 3P + E, 60A, Splashproof IP44
Combined Total Receptacle/Socket Quantity24
Alternating Phase/CircuitsYes
Receptacle/Socket Type #1U-Lock IEC C13
- Quantity on Face12
- Quantity per Breaker2
- Quantity per Phase Combination4
- U-Lock Color ID6 Circuit = Orange, Green, Blue, Light Orange, Light Green, Light Blue
- StyleIndividual
- Voltage per Receptacle/Socket208V
Receptacle/Socket Type #2U-Lock IEC C19
- Quantity on Face12
- Quantity per Breaker2
- Quantity per Phase Combination4